Seismic Design of Reinforced Masonry Shear-wall Structures
Curation progress:

The experiment contains sensor measurements, metadata, and documentation. DOI was assigned.

Complete - 03/05/2013

What's this?

The curation dashboard shows your progress as you add required elements to your project or experiment.

Complete
Incomplete
None
Cyclic Tests of Fixed-fixed CMU Wall Specimen UT-PBS-05 at UT Austin
|
DOI:10.4231/D3HT2GB60
Experiment Type: Large Scale
Description: The shear-wall specimen UT-PBS-05 with aspect ratio of 1.0 and axial load of 81.3 kips tested at UT Austin used nominal 8- x 8- x 16-in. lightweight concrete masonry units (ASTM C90); coarse grout by proportion (ASTM C476); and ASTM C270 Type S cement-lime mortar by proportion.

This folder contains all the design details, material properties, and data obtained during the test.
Dates: December 01, 2011 - December 18, 2012
Facility: University of Texas at Austin, TX, United States
Equipment:
Specimen Type: CMU Wall-UT-PBS-05
Material: CMU Wall CMU Wall (view)
Sensors: UT-PBS-05
Drawings:
Data:
Trial ( ? ) Repetition ( ? ) Interactive ( ? ) UnprocessedConvertedCorrectedDerived
Loading Trial-1..
Documentation:
Related Documents:
Analysis:
No files available
Images:
Tags (keywords):
  1. Masonry
  2. Shear Wall
  3. quasi-static
  4. reinforced masonry
Cite this work:
Farhad Ahmadi, Richard Klingner (2013). "Cyclic Tests of Fixed-fixed CMU Wall Specimen UT-PBS-05 at UT Austin", Network for Earthquake Engineering Simulation (distributor), Dataset, DOI:10.4231/D3HT2GB60